The module is designed to measure voltage -10..10 VDC and convert measured voltages to physical values:
• differential measurement mode
• hardware and software filtering
• galvanic isolation of all channels from the interface and from the power supply
Number of channels: 8, two-wire
Voltage measurement range: -10..10 V
ADC bit depth: 24
Measurement error: up to 0,1%
Full conversion time: 10 ms per 8 channels
Isolation voltage: 500 V
Power consumption: up to 0,85 W
Operating temperature: -40...75°С
Type: analog input module