MA-007

analog input module
А-15.629.54

The module is designed to measure unified current signals 0..20 mA HART and convert measured currents to physical values:

• differential measurement mode

• hardware and software filtering

• short circuit and voltage protection

• supports HART protocol

• galvanic isolation of all channels from the interface and from the power supply

Number of channels: 8, two-wire

Current measurement range: 0..20 mA, 4..20 mA, active

Maximum operating current: up to 22 mA

ADC bit depth: 24

Measurement error: up to 0,05%

Full conversion time: 10 ms per 8 channels

Isolation voltage: 1000 V

Power consumption: up to 0,85 W

Operating temperature: -40...75°С

Type: analog input module

LxWxH: 22x100x100 mm