The module is designed to measure temperature with thermocouples:
• differential measurement mode
• any types of thermocouples (configurable)
• internal and external cold junction compensation
• voltage measurement
• hardware and software filtering
• wire break diagnosis
• galvanic isolation of all channels from the interface and from the power supply
Number of channels: 8, 2 groups of 4 channels
Thermocouple types: any
Voltage measurement range: -100..100 mV
Rated input voltage: up to 100 mV
ADC bit depth: 24
Measurement error: up to 0,1%
Diagnosis: wire break
Full conversion time: 10 ms per 8 channels
Isolation voltage: 1000 V
Power consumption: up to 0,85 W
Operating temperature: -40...75°С
Type: analog input module
LxWxH: 22x100x100 mm