The module is designed to measure temperature with thermocouples and to produce 220 VAC or 24 VDC output by the alarm trip:
• any types of thermocouples (configurable)
• internal and external cold junction compensation
• hardware and software filtering
• wire break diagnosis
• galvanic isolation of all channels from the interface and from the power supply
Number of channels: 3xTC, 1xRTD, 1xDI, 1xRO NO/NC 220 VAC/24 VDC/3 A
Thermocouple types: any
Rated input voltage: up to 100 mV
ADC bit depth: 24
Measurement error: up to 0,1%
Full conversion time: 10 ms per 3 channels
Diagnosis: wire break
Isolation voltage: 1000 V
Power consumption: up to 2,5 W
Operating temperature: -40...75°С
Type: safety module
LxWxH: 22x100x100 mm