The module is designed to measure unified current signals 0..20 mA, to convert measured currents to physical values and to produce 220 VAC or 24 VDC output by the alarm trip:
• differential measurement mode
• hardware filtering
• short circuit and voltage protection
• galvanic isolation of all channels from the interface and from the power supply
Number of channels: 2xAI, 1xDI, 1xRO NO/NC 220 VAC/24 VDC/3 А
Current measurement range: 0..20 mA, 4..20 mA, active
Maximum operating current: up to 32 mA
ADC bit depth: 24
Measurement error: up to 0,05%
Full conversion time: 10 ms per 2 channels
Diagnosis: wire break
Isolation voltage: 1000 V
Power consumption: up to 2,5 W
Operating temperature: -40...75°С
Type: safety module
LxWxH: 22x100x100 mm