Designed to enter discrete signals with a voltage of 24 V DC:
• receiving NAMUR signals
• software filtering from contact rattling
• diagnostics of circuit breakage
- channels are galvanically isolated from the P-BUS bus
- explosion-proof design for placement in zone 1 or B-I
• equipped with a P-BUS interface
Number of channels: 2
Logical zero level: 0..9 V
Logical unit level: 10..28 V
Input filtering: software
Channel operating current: no more than 50 mA
Diagnostics: circuit breakage
Power consumption: no more than 1.2 W (excluding load)
Operating temperature: -40...75°C
Explosion protection marking: 1 Ex [ib] mb Gb IIB T5 X
Type: Smart Control Unit
LxWxH: 65x62x45 mm